Abstract

Smoke and fire detection, fire alarm and fire fighting systems for the Washington Metropolitan Area Transit Authority (WMATA) Mass Rapid Transit System, including some alternate fire fighting system designs, are presented. A combined rate-of-rise/fixed temperature fire detector is used in areas where rapid temperature changes are abnormal. Fixed temperature fire detectors are used in the other areas requiring protection. The below grade passenger stations have a wet pipe standpipe system. This system also includes a dry pipe and siamese connection to increase the volume and pressure of the water above the nominal city water pressure. The aerial and surface stations have a dry pipe standpipe system. All passenger station standpipe systems provide water to a hose valve within each fire equipment cabinet and to each angle hose valve located under manhole covers on the platform. The train tunnels also have a dry standpipe system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.