Abstract

In steel construction, it is often desirable for a steel member to pass through a concrete fire wall rather than being curtailed at the wall. In situations where a steel member penetrates a fire wall, the member will usually be fire protected for a certain length on each side of the wall so as to minimise the heat flow through the steel member and reduce the likelihood of ignition of combustibles on the non-fire (unexposed) side within the adjacent compartment. The testing reported in this paper suggests that it is not necessary to apply fire protection to each side of a penetrating steel member since the resulting temperature rise of the member is insufficient to cause ignition.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.