Abstract

In this study, fire behavior and resistance of unprotected H-section, partially encased (PE), and slim-floor (SF) composite beams were experimentally and numerically investigated under standard fire condition. Experimental results of this study showed that unreinforced or reinforced PE beams and reinforced SF beams can achieve the standard fire resistance of 2hours or more up to the load ratio of about 0.30. The use of fire reinforcements in SF composite beams was shown to be very effective in increasing the fire resistance time. It was again confirmed that the maximum and average temperature criteria can significantly underestimate or overestimate the realistic fire resistance of PE and SF composite beams. The test-validated coupled thermal-stress analysis indicated that the fire resistance predicted by the bending moment capacity criterion alone can be unconservative for the types of composite beams of this study. It is emphasized that the deflection-related criteria should be considered for the rational fire resistance rating of PE and SF composite beams.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.