Abstract

In this paper, we present an acoustic-structure couple interaction model of partial discharge (PD) in Gas Insulated Switchgear, the interaction between the internal acoustic source of partial discharge and structure of GIS is simulated with the finite element analysis, and the internal and external acoustic pressure levels distribution of GIS is obtained. The results based on the frequency sweep shown that the internal acoustic pressure levels is bigger than the external acoustic pressure levels of GIS in the ultrasonic frequency spectrum,it suggests that it should use the ultrasonic sensor with a broadband spectrum response to measure partial discharge in GIS, which can obtain high sensitivity. In addition, the external sound pressure of GIS is very small, and the signal of the Ultrasonic sensors must be amplified for measurement. Meanwhile, the outside acoustic pressure of the epoxy insulator is so small that it can properly judge the adjacent GIS unit partial discharge conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.