Abstract

This work develops a general finite-element (FE) model for synchronous machines. A two-dimensional, nonlinear, time-stepped finite-element simulation of a line-to-line short circuit is performed on a large salient-pole synchronous generator with multiple rotor circuits under no-load conditions. The measurements for model assessment are recorded on a 40-pole, 13.75-MVA hydrogenerator at Hydro-Quebec Rapides-des-Quinze generating station. The obtained results attest to the effectiveness of FE numerical model in performance prediction of large hydrogenerators including the saturation phenomenon.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.