Abstract
One collapse tower of 110 kV transmission line was taken as an example and a finite element model for the coupled tower-line system was established for investigating the effects of the strong wind on the transmission tower and line. The result shows that the selected standard of material of some rod members is lower, and the area of their section is relatively small. Main legs present buckling instability because of being in compression under action of the strong wind, which leads to the collapse accident of the towers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.