Abstract

New predictive methods for falling film condensation on vertical arrays of horizontal tubes using different refrigerants are proposed, based on visual observations revealing that condensate is slung off the array of tubes sideways and significantly affects condensate inundation and thus the heat transfer process. For two types of three-dimensional enhanced tubes, advanced versions of the Wolverine Turbo-C and Wieland Gewa-C tubes, the local heat flux is correlated as a function of condensation temperature difference, the film Reynolds number, the tube spacing, and liquid slinging effect. The proposed methods work best when using R-134a, as these tubes were designed with this refrigerant in mind.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.