Abstract

Abstract This experimental test investigates the effect of filling ratio (FR) and inclination angle on the thermal performance of a nanoengineered copper-water heat pipe. A hydrophilic copper oxide coating (CuO) is synthesized and integrated on the inner wall of the evaporation section of the heat pipe. The heat pipe is fabricated from an inner grooved copper pipe with dimensions of 12.7 mm outer diameter, 11 mm inner diameter, and 440 mm length. Ultra-filtered de-ionized (DI) water is used as a working fluid. Four different FRs of DI water 3%, 5%, 10%, and 15% are investigated to determine the optimum configuration. All samples are tested at various inclination angles and working loads. Experimental results show that the optimum filling ratio is the 5% FR, which was indicated by the lowest thermal resistance of 0.019 K/W.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.