Abstract
As part of a full-scale project to demonstrate the advantages of using automated process control in wastewater treatment plants, on-line sensors used in various control loops were calibrated and/or verified during control system commissioning and startup. The on-line measurements included liquid flow rates, air flow rates, suspended solids concentrations, and dissolved oxygen concentrations. The methods used to confirm instrument performance are presented along with results that show that several instruments were found to operate outside the manufacturers' written specifications. In addition, on-line methods which can help determine when recalibrations are required, and thereby help to reduce maintenance costs and ensure reliability, are also presented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.