Abstract

The optical current transformers (OCTs) using silica optical fiber as Faraday sensor were manufactured and tested in the field (275 kV substation) for 2 years to confirm their long-term reliability. Regarding the initial performance the current characteristic or the ratio error of the OCT for measurement satisfied the Japanese Electrotechnical Committee (JEC)-1201 class 1PS and that of the OCT for protection satisfied class 1T in the range from -20/spl deg/C to 55/spl deg/C. Regarding the field performance the ratio error of the OCT for measurement was stable within /spl plusmn/1% for 2 years. The current characteristic of the ratio error of the OCT for measurement satisfied class 1PS and a good result was also obtained for the OCT for protection. Also the OCTs measured accurately transient current that arose from a fault in the system. Therefor we confirm the long-term reliability of the OCT in the field through the field trial.