Abstract

A fast-acting HVDC Circuit Breaker was tested on the Pacific HVDC Intertie System. The Intertie was operated as a three-terminal system with the breaker located on one branch. Intentional faults were applied close to the breaker and 250 miles away and successfully cleared. In load-break tests the breaker disconnected one branch of the system without problems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.