Abstract

A single phase resistive type superconducting fault current limiter (SFCL) was fabricated and successfully tested in the distribution network of Chongming Island, China. This paper presents the in-grid test of the 10 kV resistive type SFCL. Firstly, the specifications of this SFCL and the target grid is introduced. Then, the working performance of the SFCL is evaluated on basis of the data obtained from both rated state test and artificial fault tests. Further discussions are carried out to verify both the current limiting function and the voltage holding function of the SFCL by the numerical model built in PSCAD.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.