Abstract
DC electronic current transformer is the data source of the system control and protection device, so its measurement delay has always been concerned. In this paper, the DC current transformer is modelled equivalently and the key factors affecting the delay of shunt and the remote module are analyzed. A field test method for the delay characteristics of the DC electronic current transformer is proposed. Moreover, a complex multi-state large current generator and integrated test system are developed. On the basis of the IEC 60044-8 standard transmission protocol, the accuracy of standard signal acquisition with the shunt is better than 0.2%. The maximum output current of the established testing system is 600 A. Based on the field test in an actual HVDC project, transient step and various frequency signal components are applied for analyzing.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.