Abstract

Energy-recovery ventilators (ERVs) are regarded as important energy-saving systems in buildings. It has been reported that they have high energy-saving rates compared with conventional ventilators that operate without energy recovery, but the saving rates have been obtained typically by employing chamber tests and simulations. In this work, a field-test method is proposed that uses a single test room but alternates the tested ventilation modes hourly. This proposed method is useful because an additional comparison room is not always available and can be a source of uncertainty for field tests. The test is performed in a classroom during a heating period, and the results are calibrated to account for different experimental conditions during the test period. The calibrated energy-saving rates indicate the effectiveness of the ERV; however, they are lower in the early hours of the system operation, for two reasons: (1) the maximum power control schemes of the heat pumps are applied for cases where the indoor temperatures are far lower than the set-point temperature; (2) the ventilation load seemingly represents a decreasing proportion of the total heating load in early hours owing to the thermal-capacity effects for the building, which was cooled for many hours. The findings are verified via a chamber test and simulations. As a consequence, it is important to account for actual system characteristics affected by the thermal behaviors of classrooms when the overall performance of a system is evaluated.

Highlights

  • As buildings become highly insulated, the proportion of ventilation loads to total building loads is increasing [1,2]

  • Energy-recovery ventilators (ERVs) have been installed in buildings to recover the energy in the controlled indoor air and to filter out pollution

  • The energy-saving effects of the energy-recovery ventilators (ERVs) mode in classrooms were reported to be similar to those in other buildings; these results were obtained via chamber tests or simulations

Read more

Summary

Introduction

As buildings become highly insulated, the proportion of ventilation loads to total building loads is increasing [1,2]. Several studies have been conducted to evaluate the energy-saving performance of ERV systems. Field measurements can be effective for evaluating the realistic energy-saving performance of an ERV. As current ERV systems have two ventilation modes, the energy-saving performance can be evaluated by alternating the modes. To evaluate the energy-saving effects of the ERV, test and comparison rooms are needed to compare the energy consumption under the different ventilation modes. The energy-saving effects of the ERV mode in classrooms were reported to be similar to those in other buildings; these results were obtained via chamber tests or simulations. It is important to understand the energy-consumption pattern of the EHP and evaluate the energy-saving effects of the ERV mode for further developments in control. Simulations are useful to verify that the pattern found in the field test is valid under dynamic conditions

Classroom Equipped with EHP and ERV
Proposed Field-Test Method for Evaluating Energy-Saving Rates
Calibration Method
Field Test and Calibration Results
Chamber-Test Results
22. KS B 6879

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.