Abstract

This study investigates the refrigeration performance of three CO2 trans-critical solutions based on field measurements. The measurements are carried out in five supermarkets in Sweden. Using the field measurements, low and medium temperature level cooling capacities and COP's are calculated for ten-minute intervals, filtered and averaged to monthly values. The results indicate that the systems using trans-critical booster system with gas removal from the intermediate vessel have relatively the highest total COP. The reasons are higher evaporation temperatures, lower internal and external superheat and higher total efficiency of booster compressors. Another important factor is gas removal from the intermediate vessel which leads to higher COP of low temperature level. Comparing the older and newer installed systems, a trend in energy efficiency improvement has been seen. The study shows this improvement originates from both changes in the system design (e.g. two stage expansion) and components efficiency improvement (e.g. higher total efficiency of compressors - lower internal superheat and higher evaporation temperatures of cabinets).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.