Abstract
Field measurements of ground fault current distribution and substation ground impedance of the LG-2 complex in Quebec, are presented. A high current measuring technique is described in Appendix A, Appendix B illustrates the way current distribution and efficiency were determined. The effectiveness of each grounding element is calculated, showing that the grounding conductors and not the ground grid drain most of the fault current.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.