Abstract

Anchor forces, ground temperatures, and piezometric pressures were measured at a retaining wall in northwestern Ontario over a period of 2 years. The anchor forces were measured with strain gauges attached in pairs directly to the anchor rods. This method appeared practical in the field for time periods of less than 2 years as long as the strain gauges were carefully protected against moisture. The anchor forces increased from an average of 5 kN initially up to values of 50 kN during the winter periods and dropped during the summer periods back to the same values measured initially. The anchor forces were largely independent of pore-water pressure variations behind the wall. Rapid drawdown conditions, however, which were experienced during the second summer, were reflected in a load increase that was equivalent to the associated unloading effect in front of the wall. The pore-water pressures behind the wall were not noticeably affected by rapid drawdown, possibly due to the restraining effect of the anchors and the high rigidity of the low sheet pile wall. Ground temperatures at or below the groundwater table never dropped below 0 °C thus restricting the depth of frost penetration. Key words : anchor loads, freezing pressure, retaining walls, pore-water pressures, ground temperatures, field measurements.