Abstract
With the increase in capacitor voltage transformer (CVT) operation life, CVT impedance changes, and the short-time switching of overhead lines, it is very easy to cause a transient oscillation accident in which a CVT participates, reduce the insulation level of a CVT, and even induce regional power grid oscillation and easily cause capacitor breakdown, after long-term operation with defects. In this paper, the whole power network, including the generator, power grid, and consumer, is modeled, and the theoretical model of the CVT ferro-resonance connected grid is built. The frequency spectrum analysis, and the measurements of resonance bus voltage and line voltage, were carried out to find the design method of a fast saturation damper (FSD) and its voltage–current characteristics that affect the vibration, based on theory and practice; this paper puts forward effective measures to reduce the resonance effect of a CVT in operation, and avoid the oscillation of the line and even the regional power grid system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.