Abstract

The results of the implementation of fire water supply requirements during the restoration and adaptation of the historical and architectural monument "Old Arsenal" in Kyiv are presented. Alternative measures of fire safety and compensation of deviations from the norms on fire protection and in particular fire water supply of the object, which is of cultural and artistic value and requires special approaches to engineering and organizational and organizational solutions are substantiated. analysis of volumetric and structural parameters of the building, which affect the engineering and organizational and organizational decisions while providing fire protection of the object. An alternative implementation of internal fire water supply for the first and basement floors of the facility is proposed, by placing external cabinets of dry pipe fire hydrant kits or external fire hydrants, which are functionally related to the internal fire water supply system. Based on the analysis of volumetric and structural parameters of the object and potential hazards that may arise, the principle of installation of external fire water supply and fire hydrants on its territory to ensure the possibility of quick connection of fire hoses and their laying through windows and pits to the premises Object. Based on the above analysis and justifications, conclusions were made on the need to amend the existing state building codes in terms of designing internal and external fire water supply.