Abstract

Many industrial sectors reject heat to the atmosphere in the form of hot water with a temperature between 40° and 70°C. This low grade heat can be upgraded by using a vapor absorption heat transformer (AHT). The present study considers a single stage AHT with binary mixture of NH3–H2O as the working fluid. The performance characteristics of the system have been evaluated by solving the governing mass and energy balance equations using a digital computer. It is found that the permissible range of concentration across the absorber is 0.04<ΔX<0.075 for the following operating conditions: Tusefulheat≤120°C,43°≤Twasteheat≤88°Cand10°≤Tsink≤27°C.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.