Abstract

Significant savings in transmission investment can result from the application of ultra-high-speed circuit breakers and relays capable of clearing faults in one-cycle primary time or five-cycle backup time as compared to a three-cycle primary and eight-cycle backup times now obtainable from conventional schemes. Stability studies were made to establish and to evaluate the gain in power transfer over typical transmission systems when the fault duration times were reduced.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.