Abstract

SummaryThe present paper investigates a travelling fire scenario in an elongated structure (Length 18 m × width 6 m × height 3 m) with a controlled fire source of six trays filled with diesel (width 4 m × length 0.5 m). The fire spread is controlled manually by initiating fires consecutively in the pools. Fire dynamics simulator (FDS) is used to a‐priori investigate variations in geometry, material data and fire load, whereas simulations using the final design and measured heat release rates (HRR) were performed after the test. The input to the model beside fire source and geometry are thermal material data. The FDS simulations were used to determine the appropriate size of the downstands (2 m from the ceiling in the final design) on the side to create a sufficiently one‐dimensional fire spread. The post‐test simulations indicate that although there are a lot of variations not included in the model similar results were obtained as in the test.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.