Abstract
This study is focused on the evaluation of thermal output of TABS (Thermally Activated Building System). The aim of this study is to evaluate TABS in terms of the temperature difference between heating medium supply temperature (<TEX>$T_s$</TEX>) and return temperature (<TEX>$T_r$</TEX>), thermal output and the surface temperature distribution according to the design flow rate and the design flow temperature. Through the transient heat transfer simulation using temperature calculation using Crank-Nicolson FDM using Physibel Voltra 6.0 W, the temperature difference between <TEX>$T_s$</TEX> and ��<TEX>$T_r$</TEX>, thermal output and the surface temperature distribution of specific TABS was calculated and evaluated. The results show that specific thermal output and temperature difference at <TEX>$60^{\circ}C$</TEX> of supply water temperature were about 162 <TEX>$W/m^2$</TEX>, <TEX>$13.6^{\circ}C$</TEX> respectively.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Korean Journal of Air-Conditioning and Refrigeration Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.