Abstract

This paper describes a fault tolerant switching loop control study case for a three water tank laboratory setup with sensors and actuators redundancies. Fault diagnosis and tolerance are two main characteristics of intelligent setups when closed-loop control is used for large complex systems. Discrete adaptive LQG (linear quadratic) and Fuzzy fault tolerant controllers, for nominal situation, are presented and tested in the laboratory setup. For abrupt fault situation (structural fault), switching from one controller to another based on controller performance evaluation using PCA (principal component analysis) technique is implemented. The main contributions are: (a) proposed approach based on PCA to detect structural faults; (b) performance assessment based on performance index through Mahalanobis distance using T 2 statistics and (c) control switching between LQG and Fuzzy controllers based on the performance index. Experimental results applied to a three-tank laboratory setup in the presence of a structural fault are shown to evaluate the performance of the proposed approach.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.