Abstract
Voltage source converter (VSC) based high voltage direct current (HVdc) transmission draws more attention in recent years for the grid connection of large-scale offshore wind farms (WF). This paper proposes nine switch converter (NSC) based configuration and control strategy for the VSC-HVdc connected offshore WFs to enhance the fault ride through operation of the system. The configuration allows having both shunt and series interfaces to the onshore grid, which allows the isolation of the faulty part of the network, continuous power delivery to the healthy portion, and significant reduction of the fault current. Reduced switch count NSC is utilized at the onshore station to provide simultaneous shunt and series compensation to the electric grid. The proposed control strategy ensures full power evacuation and the dc-link voltage regulation during network disturbances. The comparative analysis between the proposed and conventional VSC-HVdc systems carried out in MATLAB/ Simulink environment revealed the former's enhanced transient performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: IEEE Transactions on Power Delivery
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.