Abstract
Six-phase lines utilize right-of-way more efficiently than double circuit three-phase lines, and may be used to meet increasing power transmission demand. However, accurate relaying and fault location algorithms must be developed for six-phase lines. Since six-phase lines are not ideally transposed in the same manner as conventional three-phase lines, fault location using traditional symmetric component methods would result in errors for six-phase systems. Accurate fault location estimation for a six-phase line can be achieved using its impedance matrices, without assuming conductor transposition. The distance to the fault is calculated using the unsynchronized voltage and current phasors from both ends of a faulted line. The synchronization error is considered to be an additional unknown parameter. The fault location technique was tested on a simple transmission system. The distance calculation and the synchronization error estimate were both very accurate.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.