Abstract

In this article, the generation of fault gases in FR3 fluid was investigated under various thermal stresses using a sealed vessel with full fluid circulation, and the results were compared with Gemini X under similar conditions. The DGA measurements from an online dissolved-gas monitor were generally comparable with laboratory analysis. The FR3 is more thermally stable than Gemini X, as indicated by less free gas-bubble formation, less violent fluid convection, and less fault gas generation above 300°C.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.