Abstract

In modern power systems or new energy power stations, the medium voltage circuit breakers (MVCBs) are becoming more crucial and the operation reliability of the MVCBs could be greatly improved by online monitoring technology. The purpose of this research is to put forward a fault diagnosis approach based on vibration signal envelope analysis, including offline fault feature training and online fault diagnosis. During offline fault feature training, the envelope of the vibration signal is extracted from the historic operation data of the MVCB, and then the typical fault feature vector M is built by using the wavelet packet-energy spectrum. In the online fault diagnosis process, the fault feature vector T is built based on the extracted envelope of the real-time vibration signal, and the MVCB states are assessed by using the distance between the feature vectors T and M. The proposed method only needs to handle the envelope of the vibration signal, which dramatically reduces the signal bandwidth, and then the cost of the processing hardware and software could be cut down.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.