Abstract
Fault diagnosis of actual large-power high-voltage windings using transfer function method The transfer function (TF) method is presently a well-known method used to detect various types of winding damage in power transformers. Although abundant research has been done on this subject using laboratory windings as test objects, it is hard to find one, whose test objects are actual large-power transformer windings. Hence, a 400 kV disc winding consisting of 86 discs is used in this paper to study turn-to-turn short circuit with the help of the TF method. To evaluate the effects of this type of fault on TF curves, some mathematical comparison algorithms are used in this research.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.