Abstract

The failure of insulation between control coils is an important cause of circuit breaker failure, from the perspective of engineering application, it is expected to accurately screen out this kind of indiscernible inter-turn fault, an effective diagnostic method must be explored. First, apply high-voltage dc (HVDC) pulse excitation to the control coil of the high-voltage circuit breaker, and the response voltage signal is denoised by continuous wavelet transform (CWT) to obtain the main frequency signal which can reflect the essential characteristics of the response; the V/t characteristic curves of the electromagnet coils are then compared with those of standard electromagnet coils at the same frequency and at the same voltage; finally, the variation rules of the integral flux and reluctance of the electromagnet coil under test are judged, so as to judge the inter-turn insulation fault.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.