Abstract

The first industrial demonstration of a three-phase, HTS power transmission cable at the Southwire manufacturing complex is in progress. One crucial issue during operation of the 30-m HTS cables is whether they can survive the fault current (which can be over an order of magnitude higher than the operating current) in the event of a short circuit fault and how HTS cables and the cryogenic system would respond. Simulated fault-current tests were performed at ORNL on a 5-m cable. This single-phase cable was constructed in the same way as the 30-m cables and is also rated for 1250 A at 7.2 kV AC line-to-ground voltage. Tests were performed with fault-current pulses of up to 15 kA (for 0.5 s) with pulse lengths of up to 5 s (at 6.8 kA). Although a large voltage drop was produced across the HTS cable during the fault-current pulse, no significant changes in the coolant temperature, pressure, or joint resistance were observed. The cable survived all 15 simulated fault-current shots without any degradation in its V-I characteristics.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.