Abstract

Electronically triggered fault-current limiters have been used in medium- and high-voltage power distribution systems to limit the available short-circuit current to a lower level, so that the underrated switchgear can be operated safely. However, to insure a safe and proper usage of these devices, the following major operating parameters need to be considered: (1) selection of trigger level; (2) selection of di/dt; (3) effect of the capacitor bank and stray capacitances; and (4) coordination between these devices and phase overcurrent (o/c) relays at the faulted breaker. This paper will examine these major operating parameters, evaluate the performance of the current limiters under various simulated fault conditions, and develop application guidelines for current limiters.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.