Abstract

Numerical calculations of parameters of an electrical power network where an HTS fuse is used as a fault current limiting device have been done. The calculations were performed for networks containing different types of HTS cables as well. The design of HTS fuse was developed based on the numerical calculation for the network-rated parameters considering the special types 2G HTS tape characteristics. The distinctive feature of these tapes is the minimal thickness (about 30 µm) of the substrate at the critical current 450-600 A. The tests were performed at a voltage of 1 kV and demonstrated the ability of circuit breaking at fault currents about 3-4 kA. A comparison of experimental results with the calculations allows us to conclude that the HTS fuse of this design can operate as a fault current limiting device in electrical power networks at various rated voltage levels.