Abstract

Transformers represent one of the oldest and most mature elements in a power transmission and distribution network. The new superconducting transformers are smaller and lighter than conventional ones and they have lower power losses, too. Also, the new 2G superconducting tapes with high resistivity in the normal state allow to build transformers with high short-circuit strength. The short-circuit current limiting feature of the superconducting transformer, which is the most important benefit of replacing conventional windings by superconducting ones, provides protection and significantly reduces the wear and tear of circuit breakers and other substation power equipment. This paper describes the design and experimental investigations results of a model of a 1-phase, 8.8 kVA superconducting transformer with windings made of 2G HTS tape. A special regard is given to the ability of the device’s superconducting winding to limit the short-circuit current, in particular its equivalent resistance in normal state at a temperature of 77 K (i.e. resistance of the resistive layers of the HTS tape just after transition to the non-superconducting state).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.