Abstract
AbstractFault analyses are performed for the interconnecting system between a commercial‐scale subsonic diagonal‐type MHD generator and an ac power system through a line‐commutated inverter. The behavior of the interconnecting system is first examined for the case of single misfiring of one thyristor in the inverter. In this case, the load current increases because the inverter system is short‐circuited. Following the theory of inverter commutation, the load current decreases to the rated value and the MHD generator is restored to the rated condition. Next, the cases of a single‐line ground fault and of a three‐phase short circuit fault are investigated. The line voltage decreases and thus the load currents increase after the fault. This increase of load currents destroys the design‐point flow of the MHD generator. Phase‐control angle control of the inverters is required in order to restore the rated operation of the MHD generator. © 2001 Scripta Technica, Electr Eng Jpn, 136(1): 29–36, 2001
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.