Abstract

In order to further clarify the failure mechanism of the pillar porcelain insulator, the field inspection, the microscopic morphology analysis and material analysis of the ceramic shell of the pillar under a 35kV outdoor vacuum circuit breaker were carried out. The results show that the direct cause of the failure is the discharge between the high voltage conductor inside the porcelain sleeve and the weak part of the porcelain sleeve, and the high temperature arc leads to the bursting of the porcelain sleeve. The indirect cause of the failure is the loose porcelain of the porcelain sleeve, the existence of internal layering, uneven composition and micro-pores and other macro and micro defects, and the original defects of the inner surface of the porcelain sleeve, such as local unglazed and poor quality of the porcelain sleeve manufacturing process. In the long-term outdoor operation, the external moisture and gas penetrate into the porcelain sleeve, which leads to the deterioration of the insulation performance of the porcelain sleeve, and eventually leads to failure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.