Abstract

This study aims to conduct a comprehensive analysis of switching disinfectants from sodium hypochlorite bleach to chlorine dioxide (ClO2) in the water distribution system of Geyikbayiri, Antalya. For this purpose, bulk decay rates of ClO2 at various water temperatures were determined in laboratory studies. The study revealed ClO2 bulk decay rates of 0.12639 day-1, 0.17848 day-1, and 0.19621 day-1 at temperatures 15°C, 20°C, and 30°C, respectively. The EPANET, a widely employed computer program for simulating the extended-period behavior of hydraulic and water quality in pressurized pipes, was utilized for the analysis of the fate and transport of ClO2. A hydraulic model was first developed, calibrated, and verified using distinct data sets. The Hazen-Williams friction coefficient of the PSA was determined to be 120 by the trial-and-error method with a mean absolute error (MAE) of 0.408 m. A ClO2 model was then integrated with the calibrated and verified hydraulic model, revealing a wall decay rate of 0.01 m/day and an average MAE of 0.034 mg/l. After calibration and verification of the ClO2 model, several management scenarios were developed, and ClO2 dosing rates were determined. The study showed that ClO2 dosing rates of 0.40 mg/l and 0.45 mg/l should be applied to keep ClO2 concentrations within certain limits. PRACTITIONER POINTS: Disinfectants must maintain a sufficient residual in water distribution systems. Chlorine dioxide requires less contact time and is not affected by pH fluctuations. Modeling serves as a decision-making tool for the management of disinfectants. Bulk and wall decay rates of chlorine dioxide are crucial for management strategies. Chlorine dioxide is a good alternative as a disinfectant in such systems.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call