In this study, a new method for ultra-fast speed busbar protection is presented. The method is based on processing the incoming/outgoing current signals of lines or transformers connected to a substation busbar by the improved morphological gradient. The proposed algorithm is simple and requires neither fault detector nor fault classifier and it is immune to fault type, fault inception angle, fault resistance, and noise with SNRs down to 5 dB. It is applicable to different substation configurations or bus systems. According to the simulation results, the proposed algorithm has high security and dependability in discrimination of external and internal faults with the ultra-fast operation. Moreover, in the case of the existing two busbars in a substation layout, the proposed indices can discriminate between the faults of the two bus zones.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.