Abstract

When a fault occurs in transmission lines, first, it is detected, then classified, and finally, located by a distance protection. Having a fast fault detection approach helps saving the required time for the whole protection procedure. In this paper, a novel method for fault detection of transmission lines based on the summation of squared three-phase currents (SSC) and a moving average technique is proposed. The SSC is constant during a normal condition of the network, while it has considerable variation under a fault condition. Using a moving average concept, a criterion is defined, by which fault occurrence can be detected. The proposed fault detection method is evaluated in four different systems: a typical 5-bus system, a typical double-circuit transmission line, WSCC 9-bus system, and a laboratory small-scaled system. The results confirm a high degree of accuracy and speed of the proposed approach. Moreover, the performance of the method is compared with some other similar methods from different aspects.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.