Abstract

Horizontal falling film evaporators have the potential of displacing flooded evaporators as the standard in the refrigeration industry due to compelling advantages, such as smaller refrigerant charge and lower pressure drop. However, there is a need to improve the understanding of falling film evaporation mechanisms to provide accurate thermal design methods. In this work, falling film evaporation measurements on a single tube, a vertical row of ten horizontal tubes and a small tube bundle with three rows of 10 tubes each are presented. Two enhanced boiling tubes, the Wolverine Turbo-B5 and the Wieland Gewa-B5, were tested using R-134a and R-236fa. The tests were carried out at a saturation temperature of Tsat = 5 °C, film Reynolds numbers ranging from 0 to 3000, and heat fluxes between 15 and 90 kW m−2 in pool boiling and falling film configurations. A visualization study was performed under diabatic conditions to study the flow.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.