Abstract
When induction machines are fed by fast switching inverters, their interturn insulation is electrically more stressed than in the conventional feed. When inverters are used steep voltage pulses of high repetition frequency occur. This can cause partial discharges (PDs) leading to insulation failure. The PD inception voltage and velocity of the resulting electrical ageing depend on the voltage characteristic, insulation design and temperature. These relations were investigated using laboratory models of interturn insulation, semiconductor-based pulse generator and as PD detector an UV-sensitive photo multiplier tube.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.