Abstract

The type test of CuW/CuCrZr arc contact used for ultra-high voltage system capacitor bank switch was conducted. Through the comparative analysis of morphologies, compositions, properties and microstructures of the contact materials before and after failure, it can be found that the abnormal open of moving arc contact and the arc erosion and mechanical wear of static arc contact are the major reasons affecting the arc contact failure. The failure mechanism and main affecting factors were investigated in detail. The results showed that arc erosion and mechanical wear are the two main factors that affect the service lifetime of arc contacts used for ultra-high voltage transmission lines and cannot be ignored. Therefore, improving the arc erosion resistance and mechanical wear resistance simultaneously is the key to prepare the arc contact materials with longer lifetime.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.