Abstract
Failure analysis of cracking of a GIS aluminum shell which causes SF6 gas leak in a 220 kV substation was present. Visual inspection, microstructure observation, chemical composition and mechanical properties characterization were performed to reveal the forming mechanism of the crack. It is found that the crack is located in the region of the aluminum alloy shell that undergone welding repair. The crack is continuous and develops within the weld metal. Detailed investigation reveals that the crack initiates by the defect of lack of fusion in the welding repaired zone. The working stress induced by gas pressure, combined with the residual stress and vibration stress, results in the extension of the crack and the final leaking of SF6 gas.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.