Abstract

After failure of a refinery boiler, some cracks were detected in its tubes made of 2.25Cr-1Mo steel. The tubes were in the boiler superheater section. To determine causes of the cracking, samples were taken from the tubes, and different microscopical and analytical techniques such as scanning electron microscopy (SEM) and mechanical tests were used. Furthermore, finite element analysis (FEA) was used to evaluate the stress conditions in one of the cracked tubes. The results of analysis showed that the tube material was in accordance with the ASTM A213 chemical composition requirement however based on the calculated J-factor, the material was susceptible to temper embrittlement. The FEA results showed tensile residual stress formed at welding zone due to non-alignment before tubes welding. Considering the intergranular propagation of the cracks, the hardness of HAZ and other findings, it was concluded that stress corrosion cracking was the major damage mechanism.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.