Abstract

One tube was cracked used in the primary reformer furnace in a fertilizer plant for two and half years. In order to find out the causes of cracking, the methods for chemical composition analysis, macro- and microstructure analysis, penetrant testing, weld analysis, crack and surface damage analysis, mechanics property analysis, high temperature endurance performance analysis, stress and wall thickness calculation were adopted. The integrated assessment results showed that the carbon content of the tube was in the lower limit of the standard range; the tube effective wall thickness was too small; local overheating leads to tube cracking in use process.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.