Abstract

Cracking of hexagonal brass connector of a boiler tubing assembly caused leakage and interruption of the function of a water heating circuit. Destructive damage was provoked after two years in service. Visual examination, light and scanning electron microscopy coupled with local elemental energy dispersive X-ray spectroscopy (SEM/EDS) were used as the principal analytical techniques for the present investigation. The collected investigation findings suggest that failure was induced via progressive cracking, attributed probably to fatigue initiated from surface flaws existed on the thread root surface. Recommendations mainly concerned revision of the alloy selection and quality assurance of tubing assembly procedure during installation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.