Abstract

This paper presents the factors that influence ampacity and temperature rise of three-phase, single-core 33- and 500-kV XLPE underground cables (UGC) using CYMCAP software. These factors are conductor cross-sectional area, soil thermal resistivity, cable burial depth, cable separation, sheath bonding, bedding and backfill heights and thermal conductivities, nearby parallel heat source, formation of dry zone, loss tangent and segmented conductors. Results reveal that increasing the separation distance between phases gives higher ampacity, contrary to the burial depth. The rate of conductor temperature reduction due to the increase in the bedding thermal conductivity is more pronounced than that achieved by increasing backfill thermal conductivity. Furthermore, increasing the native thermal conductivity and/or the maximum conductor temperature increases the UGC ampacity and consequently increases the induced sheath voltage. Sheath losses are significant in transmission UGC where the load currents are always high. High conductor temperature and hence degradation rate is expected for UGC carrying currents of highly fluctuating loads. UGC must be derated as they age (increasing loss tangent), or when dry zones are formed around them, or when a nearby parallel heat source. Finally, it is found that the increase in the number of conductor segments nonlinearly increases the UGC ampacity.