Abstract

AbstractThis paper introduces a theoretical study of the significant factors that affecting the dynamics of wire particles in a horizontal coaxial gas‐insulated transmission line (GITL) and/or gas‐insulated switchgear (GIS) systems. The dynamics of the particle is investigated using a computational algorithm and under different voltage waveforms, gas pressures and coating thicknesses. The simulated voltage waveforms are the 60 Hz AC, single and successive switching impulses (SI), and bipolar‐oscillatory and damped impulses. All the applied voltage waveforms are simulated with and without the DC prestress, except for the AC case. These voltages represent the actual waveforms that occur in practice. The present work highlights the dangerous situations of the particle dynamics and their methods of mitigation. Moreover, the investigated dynamic behaviours of such defect under AC energization give excellent signs for the recognition by the acoustic detection technique.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.