Abstract

This paper presents an extremum seeking control (ESC) scheme for energy efficient operation of chilled-water system, and Modelica based dynamic simulation models for demonstrating the effectiveness of the proposed control strategy. The simulated plant consists of a water-cooled screw chiller and a mechanical-draft counter-flow wet cooling tower. The ESC scheme takes the total power consumption of chiller compressor and tower fan as feedback, and uses the fan speed setting as control input. The inner-loop controllers for the chiller operation include two PI control loops for regulating the evaporator superheat and the chilled water temperature. Simulation was conducted for different scenarios. The simulation results demonstrated the effectiveness of the proposed ESC strategy, and the potential for energy saving is also evaluated. Also investigated is the ESC windup issue caused by the limitation of the fan's maximum operation speed. A back-calculation anti-windup ESC scheme is applied and its effectiveness is validated by simulation results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.