Abstract

This work presents the single- and two-phase results of a parametric study investigating the performance of oblique jet arrays impinging at 45 deg on a 3.63 cm2 square copper heater surface using R-245fa. It was found that the parameters that most impact heat transfer changed as the system progressed from single- to two-phase flow behavior. The single-phase performance was governed by the jet geometry and the volumetric flow rate, while in the two-phase region, heat transfer performance was primarily affected by the fluid conditions and the heat flux applied. A single-phase correlation was developed to capture the low heat flux response, and the two-phase results were well-correlated by a pool boiling correlation. A new general correlation for jet impingement heat transfer with phase change is presented combining these correlations. Critical heat flux (CHF) data were compared with literature correlations and a new correlation was developed for arrays of boiling jets.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.